6-5
Step 5 - Close the outlet ball valve. Plug the
disconnected outlet pipe on the System side with
a ¾” MNPT Hex PVC plug at the end of the
Stainless Steel flexhose.
Step 6 - If using an External Prefilter, drain the
External Prefilter Housing (refer to section 6.3.2.3),
remove the External Prefilter Cartridge and discard
the External Prefilter Cartridge. Replace the
External Prefilter Housing without an External
Prefilter Cartridge and close the valve on the
bottom of the External Prefilter Housing.
Step 7 Use pressure gauges to ensure there is no
System pressure. Remove System Cap using the
Cap Wrench.
Step 8 - Remove Stainless Steel Prefilter (Models
MWF4200AWS and MWF4300AWS) or Carbon
Prefilter (Model MWF4100AWS). If using a
Carbon Prefilter, discard the Carbon Prefilter. If
using a Stainless Steel Prefilter, clean and set aside
the Stainless Steel Prefilter.