PPH2RF-
HEATER
KW
 
CIRCUIT A
(Compressor, Blower & Fan)
CIRCUIT B
(Heater only)
CIRCUIT C
(Heater only)
     
X24KA
0 19.6 30 - - - - - -
5 44.6 50 - - - - - -
8 59.2 60 - - - - - -
10 69.6 70 19.6 30 50 60 - -
X36KA
0 24.1 35 - - - - - -
5 49.1 50 - - - - - -
8 63.7 70 24.1 35 39.6 40 - -
10 74.1 80 24.1 35 50 60 - -
15 99.1 100 49.1 50 50 60 - -
X48KA
0 35.7 50 - - - - - -
5 60.7 70 35.7 50 25 30 - -
8 75.3 80 35.7 50 39.6 40 - -
10 85.7 90 35.7 50 50 60 - -
15 110.7 125 60.7 70 50 60 - -
20 135.7 150 - - - - - -
20 (3 circuit) - - 35.7 50 50 60 50 60
X60KA
0 45.2 70 - - - - - -
5 70.2 90 45.2 70 25 30 - -
8 84.8 100 45.2 70 39.6 40 - -
10 95.2 110 45.2 70 50 60 - -
15 120.2 125 70.2 90 50 60 - -
20 145.2 150 - - - - - -
20 (3 circuit) - - 45.2 70 50 60 50 60

 If electric heat is installed, and the overcurrent rating exceeds 60A, internal circuit breakers
must be installed in addition to branch circuit protection at the distribution panel.