ATTENTION INSTALLING PERSONNEL
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
Installer: Affix all manuals adjacent to the unit.
These furnaces comply with requirements em-
bodied in the American National Standard / Na-
tional Standard of Canada ANSI Z21.47·CSA-
2.3 Gas Fired Central Furnaces.
As a professional installer, you have an obligation to know the product better than the customer.
This includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual.
Pay special attention to all safety warnings. Often during installation or repair, it is possible to place yourself
in a position which is more hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product safely and to know it well enough
to be able to instruct a customer in its safe use.
Safety is a matter of common sense...a matter of thinking before acting.
Most dealers have a list of specific, good safety practices...follow them.
The precautions listed in this Installation Manual are intended as supplemental to existing practices.
However, if there is a direct conflict between existing practices and the content of this manual,
the precautions listed here take precedence.
NOTE: Please contact your distributor or our website listed below
for the applicable Specification Sheet referred to in this manual.
G
OODMAN
WILL
NOT
BE
RESPONSIBLE
FOR
ANY
INJURY
OR
PROPERTY
DAMAGE
ARISING
FROM
IMPROPER
SERVICE
OR
SERVICE
PROCEDURES
.
I
F
YOU
INSTALL
OR
PERFORM
SERVICE
ON
THIS
UNIT
,
YOU
ASSUME
RESPONSIBILITY
FOR
ANY
PERSONAL
INJURY
OR
PROPERTY
DAMAGE
WHICH
MAY
RESULT
.M
ANY
JURISDICTIONS
REQUIRE
A
LICENSE
TO
INSTALL
OR
SERVICE
HEATING
AND
AIR
CONDITIONING
EQUIPMENT
.
WARNING
IO-446
7/2013
INSTALLATION INSTRUCTIONS FOR *M(H,S)8 / *D(H,S)8 / *HS8 / GME8
ADS(H,S)8 / AMEH8 GAS FURNACE
CATEGORY I )
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
Page view 0
1 2 3 4 5 6 ... 47 48

Summary of Contents

Page 1 - ADS(H,S)8 / AMEH8 GAS FURNACE

5151 San Felipe Suite 500 • Houston, TX 77056www.goodmanmfg.com • www.amana-hac.com© 2011 - 2013 Goodman Manufacturing Company, L.P.ATTENTION INSTALLI

Page 2

10HORIZONTAL I NSTALLATIONForhorizontal installations,insert the#8 x 5/8 screwfrom theliterature package.Line contact to framing is permitted when ins

Page 3

11• Radiant heat from the sun.• Light fixtures or other appliances.• Radiant heat from a fireplace.• Concealed hot or cold water pipes, or chimneys.•

Page 4

12The minimum vent diameter for the Category I venting systemis as shown:UPFLOW COUNTERFLOW40 4 Inch 4 Inch60 4 Inch 4 Inch80 4 Inch 4 Inch100 5 Inch

Page 5 - ONSIDERATIONS

13Proper ChimneyTermination?(Check 1)Chimney channelfree of solid andliquid fuelappliances?(Check 2)Change ventingarrangements (Fix 2)Crown in goodcon

Page 6 - SHIPPING INSPECTION

14CHECK 3 - CHIMNEY C ROWN C ONDITION.Damage from condensate usually shows up first in the crown.If any of the following trouble signs are present, th

Page 7 - TO THE INSTALLER

15• Extremely cold weather• Long vent connectors• Masonry chimneys with no air gap between the linerand the bricks. (In practice, this can be difficul

Page 8 - EQUIREMENTS

16FIX 4 - RELININGRelining options include B vent and flexible liners.If the chimney has diagonal offsets, B vent probably cannot beused.If B vent is

Page 9 - NSTALLATION P OSITIONS

17WIRING HARNESSThe wiring harness is an integral part of this furnace. Fieldalteration to comply with electrical codes should not be re-quired. Wir

Page 10 - HERMOSTAT L OCATION

18To ensure proper unit grounding, the ground wire should runfrom the furnace ground screw located inside the furnace junc-tion box all the way back t

Page 11 - MV K-02 120-140 290°F

19115 VOLT L INE C ONNECTION OF A CCESSORIESELECTRONIC A IR CLEANER(GME8, AMEH8, GDH8 & A/GMH8 MODELS ONLY)HIGHVOL TAGE!TOAVOIDPERSONALINJURY

Page 12

2Table of ContentsSAFETY CONSIDERATIONS ...

Page 13 - CHECKLIST S UMMARY

20HIGH A LTITUDE D ERATEIMPORTANT NOTE: The furnace, as shipped, requires nochange to run between 0 - 5500 feet. Do not attempt to increasethe firing

Page 14 - Height above any

21• Use pipe joint compound on male threads only. Pipejoint compound must be resistant to the action of thefuel used.• Use ground joint unions.• Inst

Page 15 - CHECK 6 - DILUTION A IR

22PROPANE G AS T ANKS AND P IPINGIFTHEGASFURNACEISINSTALLEDINABASEMENT,ANEXCAVATEDAREAORCONFINEDSPACE,ITISSTRONGLYRECOMMENDEDTOCON

Page 16 - HIGHVOL TAGE!

23When the furnace is used in connection with a cooling unit, thefurnace should be installed in parallel with or on the upstreamside of the cooling un

Page 17

24CIRCULATION A IR F ILTERSOne of the most common causes of a problem in a forced airheating system is a blocked or dirty filter. Circulating air filt

Page 18 - SETTING THE H EAT ANTICIPATOR

25START-UP PROCEDURE AND ADJUSTMENTFurnace must have a 115 VAC power supply properly connectedand grounded. Proper polarity must be maintained for co

Page 19

26Pressure RegulatorAdjustment (Under Cap Screw)Gas ValveOn/OffSelectorSwitchINLETOUTLETInlet PressureTapOutlet PressureTapWhite-Rodgers Model 36G22Ga

Page 20 - GAS P IPING C ONNECTIONS

27Natural Gas Minimum: 4.5" w.c. Maximum: 10.0" w.c.Propane Gas Minimum: 11.0" w.c. Maximum: 13.0" w.c.INLET GAS SUPPLY PRESSURE9

Page 21 - GAS P IPING C HECKS

281. Turn OFF gas to furnace at the manual gas shutoff valveexternal to the furnace.2. Connect a calibrated water manometer (or appropriategas pressur

Page 22 - DUCTWORK - AIR F LOW

299. Remove regulator cover screw from the outlet pressureregulator and turn screw clockwise to increase pressureor counterclockwise to decrease press

Page 23 - UPRIGHT I NSTALLATIONS

3Table of ContentsPROPANE GAS TANKS AND PIPING ...

Page 24

30EXAMPLE:Installation’s gas heating (HTG) value: 1,000 BTU/ft3(Obtained from gas supplier)Installation’s seconds per cubic foot: 34 sec/ ft3Conversio

Page 25 - DJUSTMENT

31As shipped, the circulator blower fan will remain on for 150seconds after the gas valve closes. When a call for coolingoccurs, the circulator fan c

Page 26

32SAFETY CIRCUIT DESCRIPTIONGENERALA number of safety circuits are employed to ensure safe andproper furnace operation. These circuits serve to contr

Page 27 - INLET GAS SUPPLY PRESSURE

33RESETTING FROM L OCKOUTFurnace lockout results when a furnace is unable to achieveignition after three attempts. It is characterized by a non-func-

Page 28

34FLAME S ENSOR (QUALIFIED S ERVICER O NLY)Under some conditions, the fuel or air supply can create anearly invisible coating on the flame sensor. Th

Page 29

351 Tubular Heat Exchanger2 Pressure Switch3 Flue Pipe Connection4 Induced Draft Blower5 Gas Line Entrance6 Gas Valve7 Rollout Limit8 Junction Box9 Wi

Page 30 - TEMPERATURE RISE

361 Integrated control module will automatically attempt to reset from lockout after one hour.2 LED Flash code will cease if power to the control modu

Page 31 - AUXILIARY L IMIT CONTROL

37TROUBLESHOOTING CHART2 LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.AssociatedLED C

Page 32 - ROUBLESHOOTING

38TROUBLESHOOTING CHARTAssociatedLED Code22 LED Flash code will cease if power to the control module is interrupted through the disconnect or door swi

Page 33 - HIGHVOL TAGE!

39BLOWER PERFORMANCE DATA*M(H/S)8Tons ACat 0.5" 0.6 0.7 0.8ESP CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFMHIGH 3.0 1521 ---- 1466 --

Page 34

4Table of ContentsMAINTENANCE ...

Page 35 - OMPONENT

40BLOWER PERFORMANCE DATA*(D/H)S8Tons ACat 0.5" 0.6 0.7 0.8ESP CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFMHIGH 3.0 1353 ---- 1290 --

Page 36

41BLOWER PERFORMANCE DATAADSS8Tons ACat 0.5" 0.6 0.7 0.8ESP CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFMHIGH 3.0 1353 ---- 1290 ----

Page 37

42GME8Tons ACat 0.5" 0.6 0.7 0.8ESP CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFMT1 - YELLOW 1.5 875 ---- 793 ---- 736 ---- 674 ---- 5

Page 38

43BLOWER PERFORMANCE DATATons ACat 0.5" 0.6 0.7 0.8ESP CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFMT1 - YELLOW 1.5 875 ---- 793 ----

Page 39 - *M(H/S)8

44Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.HIGH VOLTAGE!DISCONNECT ALL POWER BEFORE

Page 40 - *(D/H)S8

45GME8 / AMEH8 WIRING DIAGRAMHIGH VOLTAGE!DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILU

Page 41 - ERFORMANCE

46*(M,D)H8 / ADSH8 WIRING DIAGRAMCAPBK(HI)AUXILIARY PROPERLY POLARIZED AND GROUNDED.SERVICING.WIRING TO UNIT MUST BEWARNING:DISCONNECT POWER BEFORE XF

Page 42

47 THIS PAGE LEFT INTENTIONALLY BLANK

Page 43

48NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE© 2013 Goodman Manufacturing Company, L.P.• Products•

Page 44 - *(M, D, H)S8 W

5GOODMANDAMAGEARISINGFROMIMPROPERSERVICEORSERVICEPROCEDURES.IFYOUINSTALLORPERFORMSERVICEONTHISUNIT,YOUASSUMERESPONSIBILITYFORANY

Page 45 - GME8 / AMEH8 W

6 CARBON MONOXIDE POISONING HAZARD - Special Warning for Installation of Furnace or Air Handling Units inEnclosed Areas such as Garages, U

Page 46 - *(M,D)H8 / ADSH8 W

7• The vent system is permanently installed per theseinstallation instructions.• A room thermostat is used to control the furnace. Fixedjumpers that p

Page 47

8A copy of the National Fuel Gas Code (NFPA 54/ANSI Z223.1)can be obtained from any of the following:American National Standards Institute1430 Broadwa

Page 48 - Quality Makes the Difference!

9 Top - 1"SideClearance - 1"Back - 0"Front Clearance - 3"Vent Pipe Clearance to Combustibles-6" using Single Wall Conne