NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Required Clearances
WARNING: BE ABSOLUTELY SURE THE DISTANCE BE-
TWEEN THE HEATER AND THE SURFACE OF ANY COM-
BUSTIBLE CONSTRUCTION IS NOT LESS THAN SHOWN
ON THIS PAGE.
Notes
Facing material that projects more than 3/4” (19mm) from
the wall is considered a mantel or side wall.
MINIMUM FIREPLACE OPENING 22-1/2” (572mm) High x
28-1/2” (724mm) Wide
Top Facing / Trim
Side Facing Material
SIDE WALL
C
E (USA)
D
B
A
COMBUSTIBLE MANTEL
Insert
Maximum Mantel Depth = 9” (229 mm)
Hearth Protection
E (Canada)
* Reduced clearances may be available for A, B, C and D
dimensions per NFPA 211 - latest edition, Standard for
Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Ap-
pliances (in Canada CSA B365 - latest edition). See section
on “Reduction of Appliance Clearance with Specified Forms
of Protection.”
** Side view of optional mantel deflector shown.
(1)Hearth extension reductions: 2” (51mm) reduction for 2”
(51mm) raised hearth. (USA & Canada) 24” minimum hearth
extension on all stoves as measured from the door opening of
the unit (16" [406mm] minimum hearth extension on all inserts
as measured from the door opening of the unit). Minimum
distance of floor protection to the side = 8” (200mm). This
is measured from the sides of the door opening in the USA
and from the sides of the insert in Canada.
(2)J = Maximum lintel depth without flue offset or smoke
deflector.
Hearth Protection
The hearth and/or floor protection must be a thermally
rated non-combustible hearth/floor protector meeting or
exceeding a thermal rating of k=.84 or equivalent with
a listed thickness of 3/4" (19mm) minimum in USA and
Canada. The covering must extend 24” (610mm) in front
of the heater and 8” (200mm) to either side (measured
from door opening in the USA and measured from the side
of the unit in Canada).
M
6-1/2”
165mm
F
**
J
G
H
Mantel
Hearth Protection
Trim
9”
229mm
Model *A *B *C *D E(1)
C310
USA-30”
CAN-787mm
USA -20”
CAN-584mm
20”
508mm
15”
381mm
8”
200mm
C310 with
mantel
and/or side
shields
22”
559mm
12”
305mm
20”
508mm
8”
200mm
8”
200mm
Model F (1) G H J(2) M
C310
24”
610mm
14-1/2”
368mm
22-1/2
572mm
5-1/4”
133mm
50-1/2
1283mm
C310 with mantel
and/or side
shields
24”
610mm
14-1/2”
368mm
22-1/2
572mm
5-1/4”
133mm
50-1/2
1283mm
Figure 4