Maytag PPA3RE Service Manual Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 12
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
7
BLOWERPERFORMANCE
Wire Size based on N.E.C. for 60° type copper
conductors.
COPPERWIRESIZE—AWG
(1%VoltageDrop)
SupplyWireLength-Feet
SupplyCircuit
Ampacity
200 150 100 50
6 8 10 14 15
4 6 8 12 20
4 6 8 10 25
4 4 6 10 30
3 4 6 8 35
3 4 6 8 40
2 3 4 6 45
2 3 4 6 50
Conversion
KW/h to Btu/h 3412.1
KW/h Btu/h
5 17060.7
8 27297.1
10 34121.4
15 51182.1
20 68242.8
Heat rise
Btu/h=CFMxΔT x1.08
ΔT= (Btu/h)/(CFMx1.08)
HEATRISEDATA(BasedonNominal10kwElectricHeatKit)
UNIT
BLOWER
SETTING
EXTERNALSTATICPRESSUREDROP-INCHESWATERCOLUMN
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
CFM
HEAT
RISE
CFM
HEAT
RISE
CFM
HEAT
RISE
CFM
HEAT
RISE
CFM
HEAT
RISE
CFM
HEAT
RISE
CFM
HEAT
RISE
CFM
HEAT
RISE
024K
Tap T1* 950 33 823 38 881 36 832 38 788 40 722 44 655 48 593 53
Tap T2** 1123 28 1100 29 1065 30 1023 31 978 32 929 34 877 36 820 39
Tap T3 1189 27 1158 27 1141 28 1084 29 1047 30 1009 31 959 33 906 35
Tap T4 1291 24 1246 25 1236 26 1195 26 1161 27 1120 28 1075 29 1031 31
Tap T5 1359 23 1320 24 1302 24 1280 25 1243 25 1205 26 1162 27 1112 28
030K
Tap T1 950 33 823 38 881 36 832 38 788 40 722 44 655 48 593 53
Tap T2** 1123 28 1100 29 1065 30 1023 31 978 32 929 34 877 36 820 39
Tap T3* 1189 27 1158 27 1141 28 1084 29 1047 30 1009 31 959 33 906 35
Tap T4 1291 24 1246 25 1236 26 1195 26 1161 27 1120 28 1075 29 1031 31
Tap T5 1359 23 1320 24 1302 24 1280 25 1243 25 1205 26 1162 27 1112 28
036K
Tap T1** 1215 26 1175 27 1130 28 1075 29 1020 31 970 33 900 35 840 38
Tap T2 1313 24 1277 25 1236 26 1190 27 1153 27 1104 29 1051 30 992 32
Tap T3 1460 22 1415 22 1385 23 1335 24 1275 25 1225 26 1170 27 1120 28
Tap T4* 1502 21 1466 22 1437 22 1388 23 1345 23 1305 24 1251 25 1204 26
Tap T5 1565 20 1525 21 1490 21 1450 22 1410 22 1370 23 1315 24 1270 25
042K
Tap T1 1375 23 1345 23 1310 24 1275 25 1240 25 1205 26 1160 27 1120 28
Tap T2** 1470 21 1435 22 1400 23 1370 23 1335 24 1300 24 1260 25 1215 26
Tap T3* 1600 20 1570 20 1535 21 1505 21 1470 21 1440 22 1400 23 1355 23
Tap T4 1715 18 1680 19 1650 19 1620 20 1585 20 1545 20 1505 21 1470 21
Tap T5 1895 17 1865 17 1830 17 1795 18 1760 18 1730 18 1695 19 1655 19
048K
Tap T1 1375 23 1345 23 1310 24 1275 25 1240 25 1205 26 1160 27 1120 28
Tap T2**
1470 21 1435 22 1400 23 1370 23 1335 24 1300 24 1260 25 1215 26
Tap T3 1600 20 1570 20 1535 21 1505 21 1470 21 1440 22 1400 23 1355 23
Tap T4* 1715 18 1680 19 1650 19 1620 20 1585 20 1545 20 1505 21 1470 21
Tap T5 1895 17 1865 17 1830 17 1795 18 1760 18 1730 18 1695 19 1655 19
X60K
Tap T1** 1390 23 1350 23 1310 24 1270 25 1240 25 1205 26 1160 27 1120 28
Tap T2 1540 21 1510 21 1480 21 1440 22 1410 22 1380 23 1340 24 1310 24
Tap T3 1700 19 1670 19 1630 19 1600 20 1580 20 1540 21 1510 21 1480 21
Tap T4* 1770 18 1740 18 1700 19 1660 19 1640 19 1600 20 1580 20 1540 21
Tap T5 2080 15 2030 16 2020 16 1970 16 1940 16 1910 17 1870 17 1840 17
NOTES:
Temperature rises shaded gray are for reference only. These conditions are not recommended.
* Denotes factory set cooling speed
** Denotes factory set electric heating speed
Page view 6
1 2 3 4 5 6 7 8 9 10 11 12

Comments to this Manuals

No comments