BLOWER PERFORMANCE PGC2TC/TL
PGC2TC/TL - 95.1% AFUE, Two Stage Gas Furnace
Model Number
&
Heating Input
(Btuh)
Motor Switch Settings
(0 = OFF, 1 = ON)
External Static Pressure (in.W.C.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
1/5 2/6 3/7 4/8 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise
*TC / TL - 060D
- 24B
(60,000)
0 0 0 0
1 0 0 0
0 1 0 0
1 1 0 0 725
0 0 1 0 810
1 0 1 0 940 56 890 59 845
795
750
700
0 1 1 0 990 53 945 56 905 58 860
820
775
735
690
1 1 1 0 1,055 50 1,015 52 970 54 930 57 890 59 845
805
760
0 0 0 1 1,135 47 1,095 48 1,055 50 1,010 52 960 55 930 57 890 59 850
1 0 0 1 1,185 45 1,145 46 1,105 48 1,065 50 1,030 51 990 53 950 56 910 58
0 1 0 1 1,250 42 1,210 44 1,170 45 1,135 47 1,095 48 1,055 50 1,020 52 980 54
1 1 0 1 1,290 41 1,255 42 1,220 43 1,180 45 1,145 46 1,110 48 1,075 49 1,040 51
0 0 1 1 1,315 40 1,275 41 1,240 43 1,200 44 1,160 45 1,120 47 1,085 49 1,045 51
1 0 1 1 1,350 39 1,315 40 1,280 41 1,245 42 1,205 44 1,170 45 1,135 47 1,100 48
0 1 1 1 1,390 38 1,350 39 1,315 40 1,275 41 1,240 43 1,200 44 1,160 45 1,125 47
1 1 1 1 1,420 37 1,380 38 1,345 39 1,310 40 1,270 42 1,235 43 1,200 44 1,160 45
*TC / TL - 80D
- 35C
(80,000)
0 0 0 0 1,125 55 1,040
960
880
795
1 0 0 0 1,205 58 1,120 63 1,040
960
875
795
0 1 0 0 1,305 54 1,225 57 1,150 61 1,070
995
915
840
1 1 0 0 1,430 49 1,350 52 1,270 55 1,190 59 1,110 63 1,030
950
865
0 0 1 0 1,525 46 1,450 49 1,375 51 1,300 54 1,225 57 1,150 61 1,075 65 1,000
1 0 1 0 1,620 43 1,540 46 1,465 48 1,390 51 1,315 54 1,240 57 1,165 60 1,090 65
0 1 1 0 1,695 42 1,620 43 1,545 46 1,465 48 1,390 51 1,315 54 1,235 57 1,160 61
1 1 1 0 1,770 40 1,700 41 1,630 43 1,555 45 1,485 47 1,410 50 1,340 53 1,265 56
0 0 0 1 1,875 38 1,805 39 1,730 41 1,655 43 1,580 45 1,510 47 1,435 49 1,340 53
1 0 0 1 1,905 37 1,840 38 1,775 40 1,710 41 1,640 43 1,575 45 1,510 47 1,445 49
0 1 0 1 1,980 36 1,910 37 1,845 38 1,780 40 1,715 41 1,650 43 1,580 45 1,515 46
1 1 0 1 2,025 35 1,960 36 1,895 37 1,830 38 1,765 40 1,700 41 1,635 43 1,570 45
0 0 1 1 2,085
2,025 35 1,960 36 1,900 37 1,840 38 1,775 40 1,715 41 1,655 43
1 0 1 1 2,135
2,070
2,010 35 1,945 36 1,880 37 1,815 39 1,750 40 1,685 42
0 1 1 1 2,200
2,145
2,090
2,035 35 1,980 36 1,925 37 1,870 38 1,820 39
1 1 1 1 2,280
2,225
2,170
2,115
2,065
2,010
1,955 36 1,900 37
1. Motor Switch Settings are for heating speeds using HEAT switches 1, 2, 3, & 4 and cooling speeds using COOL switches 5, 6, 7, & 8.
2. Two openings are recommended for airflows above 1,600 CFM if the filter(s) is (are) adjacent to the furnace.
3. Data is shown without filter.
4. Temperature rises in the table are approximate. Actual temperature rises may vary
5. Cells shaded in gray indicate a temperature rise outside of the recommended range.
6. When in low stage, the circulating airflow is 70% of the tables high value (2-stage furnaces only).