PHYSICALANDELECTRICALSPECIFICATIONS/OUTDOORUNITS
See current AHRI Directory for certified combinations and ratings.
www.ahridirectory.org
Wire Size based on N.E.C. for 60° type copper
conductors.
COPPER WIRE SIZE — AWG
(1% Voltage Drop)
Supply Wire Length-Feet Supply Circuit
200 150 100 50
Ampacity
6 8 10 14 15
4 6 8 12 20
4 6 8 10 25
4 4 6 10 30
3 4 6 8 35
3 4 6 8 40
2 3 4 6 45
2 3 4 6 50
UnitSize: 024K 036K 048K 060K
Electrical Data
Volts-Cycles-Phase
(1)
208/230-60-1
Total Amps 13.1 17.5 23.5 31.2
Delay Fuse Max.
(2)
25 35 45 60
Min. Circuit Ampacity 15.8 21.2 28.7 38
CondenserData
Coil
Area (ft
2
) 20.3 22.8 22.8 25.3
Rows - FPI 1-18 1-20 2-16 2-16
Tube Diam 3/8” OD 3/8” OD 3/8” OD 3/8” OD
Fan Motor
Type Brushless DC
Amps 2.6 2.6 2.6 3.8
HP 1/3 1/3 1/3 1/2
Compressor Data
RLA 10.5 14.9 20.9 27.4
LRA N/A N/A N/A N/A
Service Valves
Liquid Side 3/8” 3/8” 3/8” 3/8”
Vapor Side 3/4” 7/8” 7/8” 7/8”
InstallationRefrigerantVaporLineSize(Allliquidlines
3/8”OD)
0 - 24 ft. equiv. 3/4” 7/8” 7/8” 7/8”
25 - 39 ft. equiv. 3/4” 7/8” 1-1/8” 1-1/8”
40 - 75 ft. equiv.
(4)
7/8” 1-1/8” 1-1/8” 1-1/8”
75 - 100 ft. equiv.
(4)
1-1/8” 1-1/8” 1-1/8” 1-1/8”
Refrigerant Type R410A
RefrigerantCharge(oz.),15ft.lineset(factorycharge) 188
(3)
184
(3)
282
(3)
282
(3)
SoundRatings 60-72 59-71 64-73 63-72
Weight,lbs.(approximate)
As shipped 200 220 252 272
Net 191 211 243 263
(1) Operating Voltage Range: 187 vac min. to 253 vac max.
(2) HACR Type circuit breakers may be used.
(3)
Additional charge for longer line sets as follows (with 3/8” liquid lines):
3/4” vapor line: 0.6 oz per additional foot
7/8” vapor line: 0.7 oz per additional foot
1-1/8” vapor line: 0.8 oz per additional foot
Minimum outdoor temperature for heating is 0°F.
Minimum outdoor temperature for cooling is 40°F.
(4)
Refrigerant Tubing Limitations-The compressor manufacturer imposes a
maximum equivalent line set length of 100 ft. Furthermore, vertical elevation
shall not exceed 50 ft.